Voltage Drop Calculation for Building Electrical Design: Formula, Limits and Worked Examples

A voltage drop calculation finds how much voltage is lost along a cable between the source and the load. For a single-phase circuit, Vd = 2 × L × I × (R cos φ + X sin φ) / 1000. For a three-phase circuit, Vd = √3 × L × I × (R cos φ + X sin φ) / 1000, with L in meters, I in amperes and R and X in ohms per kilometer. IEC 60364-5-52, the guidance most Saudi consultants apply alongside SBC 401, recommends limits of 3% for lighting and 5% for other uses when the installation is fed directly from the public LV network, measured from the origin of the installation.
- Why voltage drop calculation matters in Saudi buildings
- The voltage drop formulas
- Voltage drop limits for Saudi projects
- Worked example 1: single-phase final circuit at 230 V
- Worked example 2: three-phase feeder at 400 V
- The mV/A/m method as an alternative
- How voltage drop calculation fits into the wider electrical design
- Common mistakes in voltage drop calculations
Why voltage drop calculation matters in Saudi buildings
A voltage drop calculation checks that every cable in an installation delivers enough voltage at its far end for the connected equipment to work as intended. It sits beside current-carrying capacity and fault withstand as one of the three tests that set a cable size, and on long feeders it is often the test that governs. On our projects in Saudi Arabia, where new LV supplies are 230/400 V at 60 Hz and many buildings have long horizontal runs to rooftop chillers, car park ventilation or remote pump rooms, the voltage drop calculation regularly pushes a cable one or two sizes above what the ampacity check alone allows. The same applies to the plant described on our chiller installation and replacement page.
Getting the voltage drop calculation right protects both performance and lifecycle. Motor torque varies roughly with the square of the supply voltage, so undervoltage at starting can stall a compressor or pump. LED drivers, UPS units and variable speed drives have defined input voltage windows, and equipment that runs near the bottom of its range runs hotter. Every volt lost in a cable is also energy turned into heat for the life of the building. The voltage base itself has changed: a 2010 Council of Ministers resolution moved the Kingdom's residential and commercial voltage system from 127/220 V to 230/400 V, and SASO notes that 127 V is still used in many parts of the country and is being phased out under the Saudi Electricity Company. The sections below set out each step of a voltage drop calculation for 230/400 V systems, with worked examples.
The voltage drop formulas
The general formulas below account for both the resistance and the reactance of the cable and for the power factor of the load. They give the drop in volts.
| Circuit type | Formula | Notes |
|---|---|---|
| Single-phase (phase and neutral) | Vd = 2 × L × I × (R cos φ + X sin φ) / 1000 | Factor 2 covers the outgoing and return conductor |
| Three-phase balanced | Vd = √3 × L × I × (R cos φ + X sin φ) / 1000 | Gives the line-to-line drop; √3 is approximately 1.732 |
| DC or purely resistive | Vd = 2 × L × I × R / 1000 | Reactance term disappears when cos φ = 1 |
Where:
- Vd is the voltage drop in volts.
- L is the one-way route length of the cable in meters.
- I is the design current of the circuit in amperes, taken from the load schedule for electrical design.
- R is the AC resistance of one conductor in ohms per kilometer at its operating temperature.
- X is the reactance of one conductor in ohms per kilometer.
- cos φ is the load power factor, and sin φ = √(1 - cos² φ).
The percentage drop is Vd divided by the nominal voltage: 230 V for a single-phase circuit and 400 V for a three-phase circuit on a Saudi 230/400 V system.
Correcting resistance for temperature
Manufacturers and IEC 60228 publish conductor resistance at 20 °C, but cables run hotter. For copper, the resistance at temperature T is R(T) = R(20) × [1 + 0.00393 × (T - 20)]. At 90 °C, the maximum continuous temperature for XLPE insulation, the multiplier is 1 + 0.00393 × 70 = 1.275. At 70 °C for PVC insulation it is 1.197. Using the maximum operating temperature is conservative and is the usual design assumption in a voltage drop calculation.
| Copper conductor (mm²) | DC resistance at 20 °C (Ω/km, IEC 60228 class 2) | Approximate resistance at 90 °C (Ω/km) |
|---|---|---|
| 4 | 4.61 | 5.88 |
| 6 | 3.08 | 3.93 |
| 10 | 1.83 | 2.33 |
| 16 | 1.15 | 1.47 |
| 70 | 0.268 | 0.342 |
| 95 | 0.193 | 0.246 |
| 120 | 0.153 | 0.195 |
For conductors up to about 120 mm², AC resistance at 60 Hz is very close to DC resistance. For larger sizes, skin and proximity effects add a few percent, and the manufacturer's AC resistance should be used. Reactance for LV multicore cables is typically around 0.07 to 0.09 Ω/km, while single-core cables laid apart have higher reactance. Take X from the cable datasheet where available.
Voltage drop limits for Saudi projects
SBC 401 is the electrical part of the Saudi Building Code, and the voltage drop guidance most Saudi consultants apply alongside it comes from IEC 60364-5-52. The recommended maximum drops between the origin of the installation and any load point are shown below.
| Type of installation | Lighting | Other uses |
|---|---|---|
| Type A: supplied directly from a public LV distribution network | 3% | 5% |
| Type B: supplied from a private LV supply (the building's own transformer) | 6% | 8% |
IEC 60364-5-52 also allows the limit to be increased by 0.005% per meter of route beyond 100 m, up to an additional 0.5%, and accepts higher transient drops during motor starting provided the equipment can tolerate them. For comparison, the informational notes to NEC 210.19 and 215.2 recommend 3% for branch circuits and 5% for feeders and branch circuits combined, as summarized by EE Power, NEC basics. Those NEC notes are recommendations, not mandatory rules.
| Source | Lighting or branch circuit | Total or other uses | Status |
|---|---|---|---|
| IEC 60364-5-52, Type A installation | 3% | 5% | Recommended in an informative annex |
| IEC 60364-5-52, Type B installation | 6% | 8% | Recommended in an informative annex |
| NEC informational notes (210.19, 215.2) | 3% branch | 5% feeder plus branch | Recommendation, not mandatory |
Many project specifications in the Kingdom are stricter than these values. A common approach is to allocate the total between the main feeder and final circuits, as the single line diagram should show, or to cap it at around 4%, and to limit the voltage at motor terminals during starting to a stated percentage. Code editions and specifications change, so always confirm the limits in the current SBC 401 edition, the Saudi Electricity Company connection requirements and the project specification before finalizing cable sizes. The International Electrotechnical Commission publishes the IEC 60364 series at iec.ch.
Worked example 1: single-phase final circuit at 230 V
A single-phase 230 V circuit supplies a load with a design current of 20 A at a power factor of 0.9. The cable is a copper XLPE two-core cable with a one-way route length of 40 m. The ampacity check, after derating, allows 4 mm². Check the voltage drop calculation.
- R at 90 °C for 4 mm²: 4.61 × 1.275 = 5.88 Ω/km.
- X (from the datasheet, approximately): 0.08 Ω/km.
- cos φ = 0.9, so sin φ = √(1 - 0.81) = 0.436.
- R cos φ + X sin φ = (5.88 × 0.9) + (0.08 × 0.436) = 5.292 + 0.035 = 5.327 Ω/km.
- Vd = 2 × 40 × 20 × 5.327 / 1000 = 8.52 V.
- Percentage: 8.52 / 230 = 3.70%.
A 3.70% drop is above the 3% lighting limit and leaves little margin within a 5% total once the upstream feeder is added. Repeat with 6 mm²:
- R at 90 °C: 3.08 × 1.275 = 3.93 Ω/km.
- R cos φ + X sin φ = (3.93 × 0.9) + 0.035 = 3.537 + 0.035 = 3.572 Ω/km.
- Vd = 2 × 40 × 20 × 3.572 / 1000 = 5.72 V, or 2.49%.
The 6 mm² cable brings the final circuit below 2.5%, which leaves room for the feeder upstream.
Worked example 2: three-phase feeder at 400 V
A three-phase 400 V feeder supplies a sub-main distribution board with a design current of 150 A at a power factor of 0.85. The cable is a four-core copper XLPE cable, route length 120 m. The ampacity check allows 70 mm² after derating for ambient temperature and grouping.
- R at 90 °C for 70 mm²: 0.268 × 1.275 = 0.342 Ω/km.
- X (approximately): 0.08 Ω/km.
- cos φ = 0.85, so sin φ = √(1 - 0.7225) = 0.527.
- R cos φ + X sin φ = (0.342 × 0.85) + (0.08 × 0.527) = 0.291 + 0.042 = 0.333 Ω/km.
- Vd = 1.732 × 120 × 150 × 0.333 / 1000 = 10.4 V.
- Percentage: 10.4 / 400 = 2.6%.
If the project allocates 2% to sub-main feeders, the 70 mm² cable fails. With 95 mm²:
- R at 90 °C: 0.193 × 1.275 = 0.246 Ω/km.
- R cos φ + X sin φ = (0.246 × 0.85) + 0.042 = 0.209 + 0.042 = 0.251 Ω/km.
- Vd = 1.732 × 120 × 150 × 0.251 / 1000 = 7.8 V, or 1.96%.
Combining this feeder with the 6 mm² final circuit from example 1 gives a total of about 1.96% + 2.49% = 4.45% from the start of the feeder to the load, which is within 5% for other uses. Any drop in the main incomer upstream must be added to that total. The 95 mm² impedance also feeds the short circuit calculation and the arc flash study for the sub-main board, and the single line diagram should carry the final size.
| Case | Cable | Vd (V) | Vd (%) | Result |
|---|---|---|---|---|
| Example 1, single-phase, 20 A, 40 m | 4 mm² Cu XLPE | 8.52 | 3.70 | Too high for lighting, tight for total |
| Example 1, single-phase, 20 A, 40 m | 6 mm² Cu XLPE | 5.72 | 2.49 | Acceptable |
| Example 2, three-phase, 150 A, 120 m | 70 mm² Cu XLPE | 10.4 | 2.6 | Exceeds a 2% feeder allocation |
| Example 2, three-phase, 150 A, 120 m | 95 mm² Cu XLPE | 7.8 | 1.96 | Acceptable |
The mV/A/m method as an alternative
Cable datasheets and many design guides publish voltage drop directly in millivolts per ampere per meter (mV/A/m). The voltage drop calculation then becomes Vd = (mV/A/m) × I × L / 1000. The tabulated value already includes the factor of 2 for single-phase or √3 for three-phase circuits, so the correct column must be used.
The mV/A/m figure is simply the bracketed term from the formula multiplied by the circuit factor. For the 95 mm² feeder in example 2, 1.732 × 0.251 = 0.435 mV/A/m at a power factor of 0.85, and 0.435 × 150 × 120 / 1000 = 7.8 V, the same answer. Tables usually list a resistive component (r), a reactive component (x) and an impedance (z). Using z gives a conservative result that ignores power factor: for the same cable, r = 1.732 × 0.246 = 0.426, x = 1.732 × 0.08 = 0.139 and z = √(0.426² + 0.139²) = 0.448 mV/A/m, which gives 0.448 × 150 × 120 / 1000 = 8.1 V, or 2.0%. For a final check, use the manufacturer's values for the exact cable construction and installation method.
How voltage drop calculation fits into the wider electrical design
A voltage drop calculation is only as good as the studies that feed it: the load schedule for electrical design, the single line diagram, and then the short circuit calculation, arc flash study and harmonic distortion in electrical systems review that reuse the same cable data. The table shows how they connect, and the sections after it cover each one.
| Study | Standard or reference | What it takes from the cable data | What changes when a cable size changes |
|---|---|---|---|
| Load schedule for electrical design | Project specification and demand factors | Design current and power factor per circuit | Every voltage drop figure on that feeder |
| Single line diagram in electrical design | Project drawings | Which feeders add together on each path | The total drop along that path |
| Short circuit calculation | IEC 60909 | Cable and transformer impedance | Prospective fault current at the downstream board |
| Arc flash study | IEEE 1584 and NFPA 70E | Fault current and clearing time | Incident energy and label values |
| Harmonic distortion in electrical systems | IEEE 519 and IEC 60364-5-52 | RMS current and neutral loading | Cable derating and neutral sizing |
Load schedule for electrical design
The load schedule lists every connected load with its rating, power factor, demand factor and phase allocation. A good load schedule for electrical design sets the design current I for each circuit and feeder, so an error here carries into every voltage drop figure. We check the load schedule for electrical design against the equipment submittals, not the early design allowances.
Single line diagram in electrical design
The single line diagram shows how power flows from the transformer or utility intake through the MDB and sub-main boards to the final distribution boards. In electrical design it fixes which voltage drops add together on each path, which is why the single line diagram must be final before the cable schedule is. A clear single line diagram also lets a reviewer trace the voltage drop calculation without opening the cable schedule.
Short circuit calculation
A short circuit calculation, usually to IEC 60909, uses the same cable and transformer impedances to find prospective fault currents. IEC 60909 applies a voltage factor c of 1.05 or 1.10 for maximum and 0.95 for minimum fault levels on LV systems, depending on the supply tolerance. The fault currents set breaker breaking capacities and confirm cable thermal withstand using the adiabatic check S = √(I²t) / k, where k is 143 for copper conductors with XLPE insulation. Because a larger cable has lower impedance, repeat the short circuit calculation whenever a cable size changes, and keep the short circuit calculation revision on the cable schedule.
Arc flash study
An arc flash study, typically to IEEE 1584 with work practices from NFPA 70E, uses the fault currents and protection clearing times to estimate incident energy at each board and to set labeling and PPE requirements. The 2018 edition of IEEE 1584 covers three-phase systems from 208 V to 15 kV. Cable changes made for voltage drop alter the fault current at the board, so the arc flash study should be updated with the final cable schedule. An arc flash study is a snapshot of the design, so date it against the cable schedule revision it used.
Harmonic distortion in electrical systems
Harmonic distortion in electrical systems comes mainly from drives, UPS units and LED lighting. It raises RMS current, which belongs in the I term of the voltage drop calculation, and it can load the neutral heavily with triplen harmonics. IEC 60364-5-52 gives reduction factors for four- and five-core cables when third-harmonic content exceeds 15%, and limits on distortion at the point of common coupling are commonly taken from IEEE 519, which sets 8% total voltage distortion for systems at or below 1 kV.
Saudi specifications typically set a design ambient well above the IEC reference of 30 °C in air, and harmonic distortion in electrical systems adds further derating, so check derated ampacity and voltage drop together.
Common mistakes in voltage drop calculations
- Using the cable's tabulated ampacity instead of the design current from the load schedule for electrical design.
- Reading route length off the single line diagram, which shows connections and not distances, instead of using the real cable route, including risers and tray detours.
- Ignoring harmonic distortion in electrical systems, which raises RMS current in the cable and the neutral.
- Using resistance at 20 °C instead of at operating temperature; for XLPE at 90 °C the true resistance is about 27.5% higher.
- Forgetting to add the upstream feeder drop to the final circuit drop.
- Ignoring motor starting current, which is typically six to eight times the running current for direct-on-line starting.
- Mixing single-phase and three-phase mV/A/m columns.
- Not repeating the short circuit calculation and the arc flash study after cable sizes change.
We carry out LV and MV distribution, MDB installation and cable management across the Kingdom, and whoever carries out the studies, we check installed cable routes against the voltage drop calculation, the short circuit calculation and the arc flash study before energization, using the final single line diagram. More detail is on our electrical and MEP services page, and the same discipline applies to the packages described under MEP contractor in Dammam. The sectors we serve, including data centers and hospitals with strict voltage tolerances, are on our markets page.