Cooling Load Calculation for Buildings in Saudi Arabia: Design Conditions and Method

A cooling load calculation determines the rate at which heat and moisture must be removed from a space to hold the indoor design temperature and humidity at peak conditions. It adds the sensible and latent gains from the envelope, solar radiation, people, lighting, equipment, ventilation and infiltration, using an ASHRAE method such as the Radiant Time Series or Heat Balance method. The result depends heavily on the design weather station: Riyadh is extremely hot and dry, while Dammam and Khobar combine high temperatures with very high humidity.
- What a cooling load calculation is
- Calculation methods in ASHRAE Fundamentals
- Components of the load: sensible and latent heat load
- HVAC design temperature in Saudi Arabia
- Dehumidification load calculation for coastal cities
- From load to equipment: common mistakes
- HVAC load calculation services in Saudi Arabia
What a cooling load calculation is
A cooling load calculation is the engineering estimate of the peak heat and moisture that an HVAC system must remove from each space, zone and building to hold the indoor design conditions. It differs from a simple heat gain tally because a cooling load calculation accounts for the delay between heat entering a building and becoming load on the air: walls, slabs and furniture absorb radiant heat and release it hours later. The result of the cooling load calculation sets the size of chillers, air handling units, ducts, pipes and electrical supply, so any error carries through the whole design.
Engineers sometimes call the same task a heat load calculation for building design, and the terms overlap, but the cooling load is the figure that sizes equipment in a hot climate. A careful cooling load calculation also separates the sensible and latent heat load, because coil selection, supply air temperature and the dehumidification strategy depend on that split. We use the cooling load calculation as the starting point for chiller, VRF and air handling selection on the projects we deliver, and this guide sets out the method, the load components and the HVAC design temperature in Saudi Arabia that drives the result. Our HVAC services page describes where that work sits in a project.
Calculation methods in ASHRAE Fundamentals
The ASHRAE Handbook, Fundamentals volume, contains the reference procedures for nonresidential cooling load calculation. Three families of method are in use.
| Method | How it works | Typical use today |
|---|---|---|
| CLTD/SCL/CLF | Cooling load temperature differences, solar cooling loads and cooling load factors from precalculated tables | Legacy method; useful for hand checks, no longer the recommended procedure |
| Radiant Time Series (RTS) | Splits each heat gain into convective and radiant parts, then converts radiant gains to load over 24 hours using time series factors | Recommended simplified method for design calculations and spreadsheet checks |
| Heat Balance (HB) | Solves conduction, convection and radiation balances at every surface and the zone air at each time step | Most rigorous; used in simulation engines and many commercial load programs |
ANSI/ASHRAE/ACCA Standard 183 sets minimum requirements for peak cooling and heating load calculations in buildings other than low-rise residential, and ASHRAE 90.1 points to it for the loads used to size systems. The same procedures underpin any heat load calculation for building design, and most projects use commercial software built on the Heat Balance or RTS procedure. The method matters less than the inputs: a precise algorithm fed with wrong glazing data, occupancy or weather will still give a wrong answer.
Components of the load: sensible and latent heat load
Sensible heat load is the heat that changes air temperature, and latent heat load is the heat carried by moisture that changes humidity. Every component contributes sensible heat, and some also contribute latent heat, so separating the sensible and latent heat load is essential for coil selection.
| Component | Sensible | Latent | Key inputs |
|---|---|---|---|
| Walls and roofs (conduction) | Yes | No | U-value, area, orientation, surface color, thermal mass |
| Glazing conduction | Yes | No | Glass U-value and area |
| Solar gain through glazing | Yes | No | SHGC, orientation, shading, interior blinds |
| People | Yes | Yes | Occupancy density, activity level, schedule |
| Lighting | Yes | No | Installed power density, schedules, fraction to return air |
| Equipment and plug loads | Yes | Sometimes | Equipment lists, diversity, kitchen hoods |
| Ventilation (outdoor air) | Yes | Yes | Outdoor air rate, outdoor design condition |
| Infiltration | Yes | Yes | Envelope tightness, building pressurization |
Envelope and solar
Conduction through opaque walls and roofs follows q = U × A × ΔT, adjusted for solar heating of the outer surface and thermal mass. Solar gain through glazing is usually the largest envelope component, especially on west and east facades, so the solar heat gain coefficient (SHGC), shading and window-to-wall ratio drive the peak. SBC 601, the Saudi energy conservation code for non-residential buildings, and SBC 602 for residential buildings set envelope requirements that should be reflected in the load model.
People, lighting and equipment
ASHRAE tabulates heat gain from occupants by activity. For moderately active office work the table gives approximately 75 W sensible and 55 W latent per person. Lighting gains should use the actual design lighting power, and equipment loads should come from real equipment schedules with diversity, not nameplate totals, which overstate the load.
Ventilation and infiltration
Outdoor air is often the single largest load in humid coastal cities. Ventilation rates come from ASHRAE Standard 62.1 or the applicable code; for office space the 62.1 rates are 2.5 L/s per person plus 0.3 L/s per square meter. The air-side load equations, at standard air density, are:
| Load | SI units | IP units |
|---|---|---|
| Sensible | q (W) = 1.23 × airflow (L/s) × temperature difference (K) | q (Btu/h) = 1.08 × cfm × ΔT (°F) |
| Latent | q (W) = 3010 × airflow (L/s) × humidity ratio difference (kg/kg) | q (Btu/h) = 0.68 × cfm × Δ grains per lb |
| Total | q (W) = 1.20 × airflow (L/s) × enthalpy difference (kJ/kg) | q (Btu/h) = 4.5 × cfm × Δh (Btu/lb) |
These constants assume sea-level air. At Riyadh's elevation of 608 m, atmospheric pressure is about 94 kPa and air density is roughly 7 percent lower than at sea level, so the constants should be corrected.
HVAC design temperature in Saudi Arabia
HVAC design temperature in Saudi Arabia should come from published climatic design data for the nearest representative station. ASHRAE publishes several cooling design cases for each station: a dry-bulb case with mean coincident wet-bulb, an evaporation (wet-bulb) case and a dehumidification (dew point) case, each at 0.4, 1 and 2 percent annual frequency. The 0.4 percent condition is exceeded for only about 35 hours in a typical year. The table below uses a second, Saudi source: Saudi Aramco SAES-A-112, 2006 edition, which defines summer design conditions as the values exceeded for 1% of the hours from June to September, about 30 hours.
| Item | Riyadh | Dhahran (next to Dammam and Khobar) |
|---|---|---|
| Elevation | 608 m | 89 m |
| Summer design dry-bulb, 1% | 44 °C, with mean coincident wet-bulb 21 °C | 45 °C, with mean coincident wet-bulb 26 °C |
| Summer design wet-bulb, 1% | 22 °C, with mean coincident dry-bulb 34 °C | 32 °C, with mean coincident dry-bulb 38 °C |
| Highest recorded temperature | 49 °C | 51 °C |
| Mean daily range, August | 16 K | 12 K |
| Humidity ratio at the design wet-bulb (calculated) | About 12.9 g/kg, dew point about 17 °C | About 28.4 g/kg, dew point about 30 °C |
The last row is calculated from the published dry-bulb and wet-bulb values at each station's atmospheric pressure. It shows the contrast that matters for design: outdoor air at Dhahran's design wet-bulb carries more than twice the moisture of Riyadh's, even though the dry-bulb temperatures are close. Coastal stations nearby report even higher design wet-bulb values, 34 °C at Qatif and 33 °C at Ras Tanura. The same standard gives a usual airborne dust concentration of 1 mg/m³, rising to 500 mg/m³ in sandstorms, which affects filter selection and fan heat.
These values are published figures and they vary by station and edition. ASHRAE's annual 0.4 percent values for the same stations differ from them, so always confirm the exact figures against the current ASHRAE climatic design data for the specific station, and check any project or authority requirements that set a different HVAC design temperature in Saudi Arabia for the site. Indoor design conditions for comfort cooling are commonly around 23 to 24 °C with 50 percent relative humidity or lower, subject to the project specification.
Dehumidification load calculation for coastal cities
A dehumidification load calculation is the check that a system can hold indoor humidity when outdoor moisture, not temperature, is at its peak. In Dammam and Khobar the peak dew point usually occurs at a lower dry-bulb than the peak temperature, so a system sized only for the dry-bulb case can leave spaces cool but damp. A dehumidification load calculation should always accompany the dry-bulb case.
A worked illustration shows the scale. Assume 1,000 L/s of outdoor air at the Dhahran design wet-bulb condition above (38 °C dry-bulb, 32 °C wet-bulb, humidity ratio about 28.4 g/kg at station pressure) and an indoor condition of 24 °C at 50 percent relative humidity (about 9.4 g/kg):
| Step | Calculation | Result |
|---|---|---|
| Latent load | 3010 × 1,000 × (0.0284 - 0.0094) | About 57 kW |
| Sensible load | 1.23 × 1,000 × (38 - 24) | About 17 kW |
| Sensible heat ratio | 17 / (17 + 57) | About 0.23 |
| Total, in tons of refrigeration | 74 kW / 3.517 kW per TR | About 21 TR |
In this example the latent load is more than three times the sensible load from the same outdoor air, and the sensible heat ratio is far below the 0.7 to 0.8 that many comfort coils are selected for. At Riyadh's design condition (34 °C, 22 °C wet-bulb) the same airflow gives roughly 12 kW sensible and 9 kW latent, before the altitude correction, so the split reverses. Strategies for the coastal case include dedicated outdoor air systems, energy recovery to pre-condition outdoor air, deep cooling coils with a low leaving air dew point, and controls that prioritize humidity. The result of a dehumidification load calculation is also a good check on the air handling selections described on our HVAC contractor in Dammam page.
From load to equipment: common mistakes
The result of a heat load calculation for building design feeds several other design quantities. The table shows where each output goes next, with the related guides on this site.
| Load output | What it drives | Related page |
|---|---|---|
| Sensible and latent split | Coil selection and supply air condition | HVAC services |
| Peak block load | Chiller or VRF capacity | Chiller installation and replacement and VRF and VRV systems |
| Airflow | Fans, ducts and air handling units | HVAC contractor in Riyadh |
| Electrical demand | Feeders, starters and cable sizes | Electrical and MEP services and voltage drop calculation |
Oversizing is expensive because it persists for the life of the plant. SEEC notes that air conditioning units alone consume over half of the electricity produced in the Kingdom (SEEC, via Saudipedia), so a plant that runs at poor part load wastes energy every cooling season. The mistakes below are the ones we see most often.
- Adding safety factors at every stage, on loads, on airflow and on chiller selection, which produces oversized plant that runs inefficiently at part load.
- Summing zone peaks, when the building block load is lower than the sum of zone peaks because the sun moves; plant should be sized on the coincident block load.
- Using nameplate equipment ratings instead of measured or diversified loads, which inflates the result.
- Skipping the dehumidification load calculation, so coils are selected on sensible load alone, which leads to high humidity, condensation and mold risk in coastal buildings.
- Using the wrong weather station, such as Riyadh data for a Khobar project or the reverse, which misstates both temperature and humidity.
- Skipping a check against operation: for existing buildings, logged plant data should be compared with the calculated load before a replacement chiller is sized.
HVAC load calculation services in Saudi Arabia
For new projects, the consultant's load calculation forms part of the design basis. For retrofits and replacements, a fresh heat load calculation for the building, validated against operating data, often shows that the original plant was oversized or that the use of the building has changed. As part of our HVAC load calculation services in Saudi Arabia, we review load calculations, including the dehumidification load calculation, during design and build, plant replacement and retrofit work, and we coordinate the result with chiller selection, air distribution, electrical capacity and controls. The sectors we serve are listed on our markets page, and detailed climatic data and load calculation procedures are published by ASHRAE. For a wider view of our technical guidance, see the White Arch blog.